LBI Series
Product Description
Designed for the termination of primary winding leads at the front plate of fluid (mineral oil, silicone oil, and seed-based oil or an approved equivalent) filled sidewall mounting apparatus.
Technical Specification
Rated voltage |
15kV ,25kV |
---|---|
Rated Current |
200A |
Product Type Number |
LBI120 ,LBI220 |
Product Category |
Bushing Insert |
Categories: Pad-mount TR Components, Loadbreak Series
Technical Specification
Special Description:
- Designed and manufactured in accordance with the requirements of IEEE Std 386TM-2016, standard for separable insulated connector systems. For external attachment and allow interchangeability with similarly designed bushings used on many types of pad-mounted transformers.
Table 1 - Electrical Data
Voltage Ratings | 15kV | 25kV |
Continuous Current | 200Amp | |
Withstand Voltage | 34kV | 45kV |
Impulse Voltage Withstand | 95kV | 125kV |
<3pC | 11kV | 19kV |
Operating Voltage | ||
Maximum Phase-to-Phase | 14.4kV | 26.3kV |
Maximum Phase-to-Ground | 8.3kV | 15.2kV |
Short Time Current | 10kA sym. for 0.17s 35kA sym. for 3.0s | |
Type Number | LBI120 | LBI220 |
Table 2 – Standard accessory attachment pack Information
Type Number | Accessory | Qty |
LBI120 | Shipping Cap (not for energized operation) Silicone Lubricant Installation Manual | 1 1 1 |
LBI220 |
Note: